TALAVERA WATER DISTRICT has floated a tender for Design and Construction of 350 Cubic Meter Glass Fused to Steel Tank Expandable to 700 Cubic Meter. The project location is Philippines and the tender is closing on 21 Aug 2024. The tender notice number is 2024-076, while the TOT Ref Number is 105782351. Bidders can have further information about the Tender and can request the complete Tender document by Registering on the site.

Expired Tender

Procurement Summary

Country : Philippines

Summary : Design and Construction of 350 Cubic Meter Glass Fused to Steel Tank Expandable to 700 Cubic Meter

Deadline : 21 Aug 2024

Other Information

Notice Type : Tender

TOT Ref.No.: 105782351

Document Ref. No. : 2024-076

Competition : ICB

Financier : Self Financed

Purchaser Ownership : Public

Tender Value : PHP 9000000.00

Purchaser's Detail

Name :xxxxxxxxx

Address : xxxxxxxxx

Email : xxxxxxxxx

Login to see details

Tender Details

Tender are invited for Design and Construction of 350 Cubic Meter Glass Fused to Steel Tank Expandable to 700 Cubic Meter

Procurement Mode : Public Bidding

Classification : Civil Works

Category : Construction Projects

Contract Duration : 60 Day/s

Budget for the Contract : PHP 9, 000, 000.00

Area of Delivery : Nueva Ecija

Description : 1 lot Design and Construction of Glass Fused to Steel Tank, including foundation ( soil bearing test included), tank cover, tank structure, and appurtenances conformed to latest edition NSCP and UBC 1997 with minimum 30 years design life.

GLASS FUSED TO STEEL TANK SPECIFICATIONS



A. Tank Design



The tank must be designed suitable for seismic zone 4, 15 psf Deck Live Load and a Maximum Wind Speed of 200 mph.



B. Tank Details



Net Capacity : min. 350cum expandable to 700cum

Diameter : max. of 12m

Height : min. of 3.5m

Floors : Glass fused to steel Wall

: Glass fused to Aluminum Dome Roof



Glass Fused to Steel with Level Indicator, Aluminum Dome roof, Vent and Internal & External Ladders



Glass Fused to Steel Tank Accessories:



1. Silicone sealants applied on the tank wall

2. Exterior Reinforcing Ring.

3. 1 x Manway 24 " installed on the tank wall

4. 1 x Vertical Cage Ladder with a 1x1M platform.

5. Aluminum Deck Roof with HDG Perimeter Handrail

6. Magnetic Water Level Indicator



Specification of Glass Fused to Steel Tan...

Documents

 Tender Notice