Tenders are invited for Design, Build, Finance, Own, Operate, and Transfer 02 Mwp Grid-Tied Solar Photovoltaic System and Batery Storage System in ha.hoarafushi Island
The solar farm RMU shall have the following general configuration:
· Ring switches
2
· Circuit breakers
1
Enclosure
· IP Rating
IP65
· Rain shield
Yes
· Lifting rings
minimum2, OEM to confirm suitability
· Colour
to be specified
· Paint
ISO C5 Marine Grade Paint coated enclosures
· Height above ground
Base must be mounted a minimum of 500 mm above the local ground surface to reduce potential for inundation.
Circuit Breakers
· Type
Vacuum
· Rated current
200A
· Closing (Motor driven charging)
Yes
· Spring recharge after closing
Yes
Ring Switches
· Remote operation capability
Yes
Safe operating procedures for closure to be established between Contractor and Grid Operator. Grid Operator shall have authority for remote disconnect if required for system safety or stability (dispatch control to be used preferentially).
Earth Switches
· Type
Fault making
· Making capacity
40 kA peak
· Circuit earth switch interlock
Yes, with associated circuit breaker
· Remote operation capability
Yes
Feeder CTs & VTs
o Contractor to specify
Feeder Protection Relay
· Required
· Functions - as detailed below.
Communications interfaces Modbus
SCADA interface Modbus
Capacitive Voltage Indication
· Required
Yes
· Electrical interlock
Contractor to specify
Surge Arrestor
· Required
Contractor to specify
Auxiliary Power
· Required
Yes
· Auxiliary equipment AC voltage
400/230 V AC
· Tripping and closing supply voltage
110 V DC
· Indication supply voltage
110 V DC
· Spring charge motor voltage
110 V DC
· Alarm supply voltage
110 V DC
· Redundant trip coils
Yes
· Redundant trip supplies
Yes
· Load
To be calculated by Contractor
· UPS power
Yes, to comprise of rectifier and battery bank
· Backup duration
Minimum 12 hours without AC supply
· Redundant DC supplies
required
Metering
· Required
Yes, as per section D.3.4 below
A Pre-Bid meeting shall take place at the following date and time:
Employer will organize an Online Video Conference Meeting via Microsoft Teams for the Pre-Bid meeting.