Procurement Summary
Country : USA
Summary : SLAC_WaterCooledCondensingUnit
Deadline : 19 Nov 2024
Other Information
Notice Type : Tender
TOT Ref.No.: 109722249
Document Ref. No. : SLAC_349035_Rev1_WaterCooledCondensingUnit
Competition : ICB
Financier : Self Financed
Purchaser Ownership : Public
Tender Value : Refer Document
Purchaser's Detail
Name :Login to see tender_details
Address : Login to see tender_details
Email : Login to see tender_details
Login to see detailsTender Details
Description
SLAC National Accelerator Laboratory is operated by Stanford University for the Department of Energy. As a management and operating contractor, subcontracts awarded by the Laboratory are not Federal procurements, and are not directly subject to the Federal Acquisition Regulations in 48 CFR. Nonetheless, certain Federal laws, Executive Orders, and regulations may affect our DOE approved purchasing system, as required by statute, regulation, or contract terms and conditions.
Water cooled condensing unit = Qty 1
Specifications:
SLAC is in the process of building a cooling plant for research and needs a refrigeration condensing unit based on a vapor compression cycle, using refrigerants with the ASHRAE refrigeration classification of A1 (low toxicity and nonflammability) and not listed at the Section 95374 - List of Prohibited Substances in CA. As example, R448A is an acceptable refrigerant.
When at full capacity, the condensing unit shall give a cooling capacity of minimum 4000 W with evaporator temperature at -40oC.
The condenser of the refrigeration circuit shall be cooled by water with an inlet temperature at 17oC (63 F).
The system shall equip with an R448a evaporator made by a compact brazed plate heat exchanger that condenses gas carbon dioxide running in counterflow. The MAWP shall be 80 bar. Example SWEP B18 with 34 plates, or similar.
The refrigeration condensing unit shall use an expansion valve with adjustable cooling temperature between -40oC and +10oC. The use of cylinder unloader and/or VFD to adjust the cooling capacity is preferred.
The system weight shall be less than 1200 lbs.
The power supply of the condensing unit shall be 460v/3ph/60hz.
The dimension of the unit shall be not larger than 48”x45”x62”
Technical evaluation criteria:
Dimensions not larger than 48”x45”x62” Refrigeration Capacity not less than 4kW at -40oC Adjustable Evaporation temperature -40 oC, +10 oC Water cool...
Active Contract Opportunity
Notice ID : SLAC_349035_Rev1_WaterCooledCondensingUnit
Related Notice
Department/Ind. Agency : ENERGY, DEPARTMENT OF
Sub-tier : ENERGY, DEPARTMENT OF
Office: SLAC Natl Accel Lab -DOE Contractor
General Information
Contract Opportunity Type: Solicitation (Original)
Original Published Date: Nov 05, 2024 01:14 pm PST
Original Date Offers Due: Nov 19, 2024 05:00 pm PST
Inactive Policy: 15 days after date offers due
Original Inactive Date: Dec 04, 2024
Initiative: None
Classification
Original Set Aside:
Product Service Code: AJ12 - GENERAL SCIENCE AND TECHNOLOGY R&D SERVICES; GENERAL SCIENCE AND TECHNOLOGY; APPLIED RESEARCH
NAICS Code: 333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipment Manufacturing
Place of Performance: Menlo Park, CA 94025 USA
Documents
Tender Notice
Reps-and-certs-Rider-September-2022.pdf
Fixed_Price_Commercial_Supplies_and_Services_Subco.pdf
01.pdf
A1_SOW_TechCriteria.pdf