KUWAIT OIL COMPANY (K.S.C) has floated a tender for Supply of Oil Immersed Conservator Type Power Transformer. The project location is Kuwait and the tender is closing on 19 Feb 2024. The tender notice number is 2128680, while the TOT Ref Number is 95659186. Bidders can have further information about the Tender and can request the complete Tender document by Registering on the site.

Expired Tender

Procurement Summary

Country : Kuwait

Summary : Supply of Oil Immersed Conservator Type Power Transformer

Deadline : 19 Feb 2024

Other Information

Notice Type : Tender

TOT Ref.No.: 95659186

Document Ref. No. : 2128680

Competition : ICB

Financier : Self Financed

Purchaser Ownership : Public

Tender Value : Refer Document

Purchaser's Detail

Name :Login to see tender_details

Address : Login to see tender_details

Email : Login to see tender_details

Login to see details

Tender Details

Quotation are invited for Supply of Oil Immersed Conservator Type Power Transformer

Rfq Fee Amount : 25

Bid Bond Amt / % : 250

70134279
Transformer, Power, 750 Kva, Rated Voltage - Primary: 11 Kv,
Secondary: 0.440 Kv, 50hz, Oil Immersed Conservator Type Power
Transformer
Oil Immersed Conservator Type Power Transformer
General Information:
Max. Relative Humidity: 100%
Mounting Type: Skid Mounted
Reference Power: 750 Kva
Service: Distribution
Ingress Protection: ip55 to Iec 60529
Radiator Type: Removable
Tank Cover: Bolted
Design Data:
Nominal Rated Voltage - Primary: 11 Kv, Secondary: 0.440 Kv
Highest Voltage to Iec 60076-3 (Rms) - Primary: 12k, Secondary: 1.1
Kv
Rated Short Duration Power Frequency - Primary: 28 Kv,
Secondary: 2.5 Kv
Rated Lighting Impulse Withstand Voltage - Primary: 75 Kv
System Earthing - Impedance Earthing, Secondary: Solid
Winding Conductor - Primary: Copper, Secondary: Copper
Disconnecting Chamber: Yes
Disconnecting Chamber Type: Oil Filled
Cable Termination Type: Heat Shrink (Raychem or Equivalent)
Cable Gland Type: Compression
Main External Termination Type - Primary: Cable Box,
Secondary: Cable Box
Tap Changer Type - Primary: Off Circuit
Tappings Required - Primary: +-2.5%, +-5%
Rated Voltage Ratio at Principal Tap at No Load - Primary:
11/0.457 Kv
Frequency: 50 Hz
No. Of Phases - Primary: 3 Phase, Tpn in the Secondary
No. Of Windings: 2 Nos.
Winding Connection Symbol to Iec 60076-1: Dynl 1
Impedance at Principal Tap at Rated Current: 5.0 %
Type of Cooling: Onan
Insulating Liquid: Mineral Oil
Accessories:
1. Oil Conservator
2. Breather (Silica Gel Type)
3. Gas & Oil Actuated Relay (Buchholz)

Documents

 Tender Notice